There is really not much to "size" on this system.
The wiring that runs from the PV array to the house power distribution panel should be sized to keep a low voltage drop.
This Application note for the 190watt inverter provides a table for choosing the gage of the wire from the array to the house:
http://www.enphaseenergy.com/downloads/EnphaseAppNote_Circuit_Calculations_M190.pdf
In my case with 10 inverters and a 90 ft run, I could have used #12 wire (good for up to 115 ft with 10 inverters), but I decided to use #10 to allow for adding a few more panels at some future date.
Ephase allows up to 15 inverters on one circuit -- this is (15)(190w/inverter) = 2850 watts. After this, a 2nd circuit has to be added.