Wire
Sizing and Ampacities Charts
12 Volt 2% Wire Loss Chart
Maximum distance one-way in feet of various
gauge two conductor copper wire from power source to load for 2% voltage
drop in a 12 volt system. You can go twice the distance where a 4% loss is
acceptable. Do not exceed the 2% drop for wire between PV modules and
batteries. A 4 to 5% loss is acceptable between batteries and lighting
circuits in most cases. Multiply distances by 2 for 24 volts and by 4 for
48 volts.
2% Voltage Drop
Chart |
Amps |
#14 |
#12 |
#10 |
#8 |
#6 |
#4 |
#2 |
#1/0 |
#2/0 |
#4/0 |
1 |
45 |
70 |
115 |
180 |
290 |
456 |
720 |
. |
. |
. |
2 |
22.5 |
35 |
57.5 |
90 |
145 |
228 |
360 |
580 |
720 |
1060 |
4 |
10 |
17.5 |
27.5 |
45 |
72.5 |
114 |
180 |
290 |
360 |
580 |
6 |
7.5 |
12 |
17.5 |
30 |
47.5 |
75 |
120 |
193 |
243 |
380 |
8 |
5.5 |
8.5 |
11.5 |
22.5 |
35.5 |
57 |
90 |
145 |
180 |
290 |
10 |
4.5 |
7 |
11.5 |
18 |
28.5 |
45.5 |
72.5 |
115 |
145 |
230 |
15 |
3 |
4.5 |
7 |
12 |
19 |
30 |
48 |
76.5 |
96 |
150 |
20 |
2 |
3.5 |
5.5 |
9 |
14.5 |
22.5 |
36 |
57.5 |
72.5 |
116 |
25 |
1.8 |
2.8 |
4.5 |
7 |
11.5 |
18 |
29 |
46 |
58 |
92 |
30 |
1.5 |
2.4 |
3.5 |
6 |
9.5 |
15 |
24 |
38.5 |
48.5 |
77 |
40 |
. |
. |
2.8 |
4.5 |
7 |
11.5 |
18 |
29 |
36 |
56 |
50 |
. |
. |
2.3 |
3.6 |
5.5 |
9 |
14.5 |
23 |
29 |
46 |
100 |
. |
. |
. |
. |
2.9 |
4.6 |
7.2 |
11.5 |
14.5 |
23 |
150 |
. |
. |
. |
. |
. |
. |
4.8 |
7.7 |
9.7 |
15 |
200 |
. |
. |
. |
. |
. |
. |
3.6 |
5.8 |
7.3 |
11 |
Maximum Ampacities for Wire
Allowable
ampacities of conductors (wires) in conduit, raceway, cable or directly
buried, based on ambient temperature of 86° F (30° C). NEC allows rounding
up cable ampacity to the next size standard fuse or breaker.
Maximum
Ampacity for Copper
and Aluminum Wire |
Wire Size |
Copper |
Aluminum |
167° F (75° C) |
194° F (90° C) |
167° F (75° C) |
194° F (90° C) |
*14 |
20 |
25 |
|
. |
*12 |
25 |
30 |
20 |
25 |
*10 |
35 |
40 |
30 |
35 |
8 |
50 |
55 |
40 |
45 |
6 |
65 |
75 |
50 |
60 |
4 |
85 |
95 |
65 |
75 |
2 |
115 |
130 |
90 |
100 |
1 |
130 |
150 |
100 |
115 |
1/0 |
150 |
170 |
120 |
135 |
2/0 |
175 |
195 |
135 |
150 |
3/0 |
200 |
225 |
155 |
175 |
4/0 |
230 |
260 |
180 |
205 |
* The national electric code (NEC) specifies that the overcurrent protection
device not exceed 30A for 10 AGW wire, 20A for 12 AGW wire and 15A for 14
AWG wire.
Properly sized wire can
make the difference between inadequate and full charging of a battery
system, between dim and bright lights, and between feeble and full
performance of tools and appliances. Designers of low voltage power circuits
are often unaware of the implications of voltage drop and wire size. In
conventional home electrical systems (120/240 volts ac), wire is sized
primarily for safe amperage carrying capacity (ampacity). The overriding
concern is fire safety. In low voltage systems (12, 24, 48VDC) the
overriding concern is power loss. Wire must not be sized merely for the
ampacity, because there is less tolerance for voltage drop (except for very
short runs). For example, a 1V drop from 12V causes 10 times the power loss
of 1V drop from 120V.
Use the following chart as your primary tool in solving wire sizing
problems. It replaces many pages of older sizing charts. You can apply it to
any working voltage, at any percent voltage drop.
Determining tolerable voltage drop for various electrical loads
A general rule is to size the wire
for approximately 2 or 3% drop at typical load. When that turns out to be
very expensive, consider some of the following advice. Different electrical
circuits have different tolerances for voltage drop.
LIGHTING CIRCUITS, INCANDESCENT AND QUARTZ HALOGEN (QH): Don't cheat on
these! A 5% voltage drop causes an approximate 10% loss in light output.
This is because the bulb not only receives less power, but the cooler
filament drops from white-hot towards red-hot, emitting much less visible
light.
LIGHTING CIRCUITS, FLUORESCENT: Voltage drop causes a nearly proportional
drop in light output. Flourescents use 1/2 to 1/3 the current of
incandescent or QH bulbs for the same light output, so they can use smaller
wire. We advocate use of quality fluorescent lights. Buzz, flicker and poor
color rendition are eliminated in most of today's compact fluorescents,
electronic ballasts and warm or full spectrum tubes. Use them to illuminate
your office so that customers can see them. (An excellent source is W.W.
Grainger, listed in your local phone book, or www.grainger.com. Get an
account with them!)
DC MOTORS may be used in renewable energy systems, especially for water
pumps. They operate at 10-50% higher efficiencies than AC motors, and
eliminate the costs and losses associated with inverters. DC motors do NOT
have excessive power surge demands when starting, unlike AC induction
motors. Voltage drop during the starting surge simply results in a "soft
start".
AC INDUCTION MOTORS are commonly found in large power tools, appliances and
well pumps. They exhibit very high surge demands when starting. Significant
voltage drop in these circuits may cause failure to start and possible motor
damage. Follow the National Electrical Code. In the case of a well pump,
follow the manufacturer's instructions.
PV-DIRECT SOLAR WATER PUMP circuits should be sized not for the nominal
voltage (ie. 24V) but for the actual working voltage (in that case
approximately 34V). Without a battery to hold the voltage down, the working
voltage will be around the peak power point voltage of the PV array.
PV BATTERY CHARGING CIRCUITS are critical because voltage drop can cause a
disproportionate loss of charge current. To charge a battery, a generating
device must apply a higher voltage than already exists within the battery.
That's why most PV modules are made for 16-18V peak power point. A voltage
drop greater than 5% will reduce this necessary voltage difference, and can
reduce charge current to the battery by a much greater percentage. Our
general recommendation here is to size for a 2-3% voltage drop. If you think
that the PV array may be expanded in the future, size the wire for future
expansion. Your customer will appreciate that when it comes time to add to
the array.
WIND GENERATOR CIRCUITS: At most locations, a wind generator produces its
full rated current only during occasional windstorms or gusts. If wire sized
for low loss is large and very expensive, you may consider sizing for a
voltage drop as high as 10% at the rated current. That loss will only occur
occasionally, when energy is most abundant. Consult the wind system's
instruction manual.
More
techniques for cost reduction
ALUMINUM WIRE may be more
economical than copper for some main lines. Power companies use it because
it is cheaper than copper and lighter in weight, even though a larger size
must be used. It is safe when installed to code with AL-rated terminals. You
may wish to consider it for long, expensive runs of #2 or larger. The cost
difference fluctuates with the metals market. It is stiff and hard to bend,
and not rated for submersible pumps.
HIGH VOLTAGE PV MODULES: Consider using higher voltage modules (18+ volts
peak power point, like our BP-585 and BP-590) to compensate for excessive
voltage drop. In some cases of long distance, the increased module cost may
be lower than the cost of larger wire.
SOLAR TRACKING: Use a solar tracker (by Zomeworks) so that a smaller array
can be used, particularly in high summer-use situations (tracking gains the
most energy in summer when the sun takes the longest arc through the sky).
The smaller PV array will require smaller wire.
WATER WELL PUMPS: Consider a slow-pumping, low power system with a storage
tank to accumulate water. This reduces both wire and pipe sizes where long
lifts or runs are involved. A PV array-direct pumping system may eliminate a
long wire run by using a separate PV array located close to the pump. Our
SunRise Submersible, Solar Slowpump, Flowlight Booster Pump and Solar Force
Piston Pump are highly efficient DC pumps that are available up to 48V. We
also make AC versions and converters to allow use of AC transmitted over
great distances. These pumps draw less running current, and far less
starting current than conventional AC pumps, thus greatly reducing wire size
requirements.
|